Description
概观
Essential details:REF615E-1G HBFDACADABC1BNN21G Feeder Protection and Control
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@saulcontrol.com
[Mobile] 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
REF615E-1G HBFDACADABC1BNN21G Feeder Protection and Control
REF615 is available in nine alternative standard configurations. The standard signal configuration can be altered by means of the graphical signal matrix or the graphical application functionality of the Protection and Control IED Manager PCM600.
Further, the application configuration functionality of PCM600 supports the creation of multi-layer logic functions using various logical elements, including timers and flip-flops. By combining protection functions with logic function blocks, the IED configuration can be adapted to userspecific application requirements.
The IED offers directional and non-directional overcurrent and thermal overload protection as well as directional and non-directional earth-fault protection. Some standard configurations allow as an option admittance-based, harmonics-based or wattmetric-based earth-fault protection to be used in addition to directional earth-fault protection. Further, the IED features sensitive earth-fault protection, phase discontinuity protection, transient/intermittent earth-fault protection, overvoltage and undervoltage protection, residual overvoltage protection, positive-sequence undervoltage and negativesequence overvoltage protection. Frequency protection, including overfrequency, underfrequency and frequency rate-of-change protection, is offered in IEDs with standard configurations H and J. The IED also incorporates optional three-pole multi-shot auto-reclose functions for overhead line feeders.
Enhanced with optional hardware and software, the IED also features three light detection channels for arc fault protection of the circuit breaker, busbar and cable compartment of metalenclosed indoor switchgear.
The arc-fault protection sensor interface is available on the optional communication module.
Fast tripping increases staff safety and security and limits material damage in an arc fault situation.