Essential details:1746-IB32 Digital DC Input Module Allen Bradley
Superiority products 1746-IB32 Digital DC Input Module Allen Bradley
- When installing the module, ensure that the power is removed from the chassis as this module does not support Removal and Insertion Under Power (RIUP). It comes with a removable terminal block that permits wiring remote to the module as well as simplified maintenance as the RTB permits insertion to another module of the same type.
The 1746-IB32 offers isolation from the backplane tested at 1500 Volts AC for 60 seconds between the backplane and the I/O and it has a 1500 Volt AC dielectric withstand. The minimum voltage across its circuit in the ON state is 15.0 Volts DC and in its OFF state, it has a maximum voltage drop of 5.0 Volts DC and a maximum leakage current of 1.5 mA. The 1746-IB32 module has a maximum signal delay time of 3ms across its inputs in the ON and the OFF mode and it has an overall nominal input current of 5.1 mA at 24 Volts DC nominal voltage. The 1746-IB32 has an operating temperature bracket between 0 and 60 degrees Celsius (32 and 140 degrees Celsius) at 5 to 95% non-condensing humidity and it has an operational vibrational withstand of 1G at 5 to 200 Hertz and a shock rating of 30G.