Description
概观
Essential details:TRICONEX 9565-810F Tricon v9–v10 Systems
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@saulcontrol.com
[Mobile] 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
MDD115A-N-030-N2M-180GA1 MDD Synchronous Motors Series
Termination panels with interposing relays can be used with most digital output modules andare recommended for these applications.
“Load currents greater than 2 amps
.Field voltages greater than 115 VAC
.Voltage-level conversions
Motor-starter circuit compatibilityInterposing relay panels are available in these configurations。16-point commoned
。16-point non-commoned
The digital outputs of the interposing relays are not fault-tolerant. However, each relayprovides an auxllary contact that can be fed into a digital input to send a loopback sianal to thecontrol program. A user-written loopback check in the control program can ensure that the relayhas achieved its commanded state. The loopback cable must be ordered separately.
Each interposing relay panel provides the capability to common power and return through afactory-mounted bus-bar arrangement.Each interposing relay panel consists of.
A7 in x 19 in (36 cm x 48 cm) rack-mountable panel with terminals for 16 digitaloutputs and 16 digital inputs.
.Two ELCO connectors mounted on the panel for connecting to digital input modulesusing digital input cables 9141-010.9142-010,or 9143-010.”An ElA standard RS-310-C plate on which the termination panel is mounted.*A digital output module and a cable compatible with the selected coil voltage.