Essential details:SR469-P5-HI-A20-H GE SR 469 motor management relays
SR469-P5-HI-A20-E-H Technical Specifications
Hi-Volt Fuse Current Rating | 2 A |
Hi-Volt Fuse Model | 215002 |
IP Class | IP20-X |
Vibration Rating | 8.0 g for 72 hours |
Impulse Test | IEC 255-5 0.5 Joule 5 kV |
Phase Current | 5 A |
Humidity | Up to 90% noncondensing |
Analog Outputs | 4-20 mA |
Shipping Weight | max. 7.7 kg |
Mounting | Panel or 19 inch rack mount |
Product Description
The SR469-P5-HI-A20-E-H, from GE Multilin, is one of the company’s SR 469 motor management relays.
The SR469-P5-HI-A20-E-H includes a conformal coating for harsh environments. This coating will extend the working life of the relay and is recommended for units going into environments where specific hazards exist. This may include corrosive agents, hydrogen sulfide, or high humidity levels.
SR469 relays were designed to offer comprehensive motor protection. They have multiple RTD inputs; these are used for stator thermal protection. The units include simulation functions, event reports, data logging, and waveform capture. Additionally, SR469 relays offer complete asset monitoring, including analog I/o, temperature, and full metering. They are compatible with a number of different protocols including DeviceNet, Modbus RTU, and Modbus TCP/IP.
lf you need to inquire or purchase ,please send the product models to my email or call medirectly .
sunny He
[Email] sales@xiongbagk.cn
[Mobile] 86-18059884797
[WhatsApp] 86-18059884797
[Skype] sales@saulcontrol.com
SR469-P5-HI-A20-H GE SR 469 motor management relays
The SR469-P5-HI-A20-E-H is a basic unit with 5 Amp phase CT secondaries. The unit has a control power rating of 90-300 VDC, 70-265 VAC @ 48-62 Hz. Analog outputs are 4-20 mA. The enhanced front panel includes LED indicators, an LCD 40-character display, communication port, and keypad.
GE Multilin manuals will provide a more in-depth look at this and other SR 469 modules. Datasheets from GE will also give you more information regarding this unit, including handling specifications and particular warnings that should be followed for a safe installation.