Sale!

SE4302T02 EMERSON DeltaV™ DO 24 V DC Isolated CHARM

SE4302T02 EMERSON DeltaV™ DO 24 V DC Isolated CHARM

Manufacturers :EMERSON
Model(s)  :SE4302T02
Additional Information :DeltaV™ DO 24 V DC Isolated CHARM
Estimated Shipping Size
Dimensions: 263 × 58 × 28mm
Weight:.4.3 kg
Country of Origin: United States of America

 

Categories: , SKU: SE4302T02

Description

Overview


Essential details:SE4302T02 EMERSON DeltaV™ DO 24 V DC Isolated CHARM

Device Type24 V DC Inductive Load
Ouput Range4 V DC to 32 V DC
Output Rating1.0 A continuous ( 2 A inrush for < 100 ms)
Off State Leaking Current1 mA maximum
Configurable Output BehaviorMomentary Output, Continuous Pulse Output
IsolationThe output channel is galvanically isolated and factory tested to 1000 V DC.
Field Circuit Protection4 A Current Limiting Circuit (Short Circuit) with thermal shutoff, automatic reset. Field wiring disconnect. Recommend external fuse at power source
CHARM power req.22 mA max @ 24 V DC
CHARM Heat Dissipation0.46 W

SE4302T02

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@xiongbagk.cn

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

SE4302T02 EMERSON DeltaV™ DO 24 V DC Isolated CHARM

Reduce business risks by minimizing process downtime. This solution brings device signals to DeltaV I/O from existing Foxboro I/A Series 200 I/O termination assemblies. Keeping device wires intact accelerates the new system startup, enabling you to rapidly resume production.
Save on installation costs. Eliminating new field wiring saves money and reduces the risk of errors. Time and materials savings are significant.
Preserve HART signals. Use HART® pass-through for complete diagnostics at the DeltaV Operator Station.