MTL4541-C MTL Repeater Power Supply
- Safe-area load resistance (MTLx541) : @ 24mA: 0 to 360O @ 20mA: 0 to 450O
- Safe-area load (MTLx541S) : Current sink: 600O max.
- Maximum voltage source: 24V dc
- Safe-area circuit output resistance: > 1MO
- Safe-area circuit ripple : < 50µA peak-to-peak
- Hazardous-area input : Signal range: 0 to 24mA (including over-range), Transmitter voltage: 16.5V at 20mA
- Transfer accuracy at 20°C : Better than 15µA
- Temperature drift : < 0.8µA/°C
- Response time : Settles to within 10% of final value within 50µs
- Communications supported : HART (terminals 1 & 2 only)
- LED indicator : Green: power indication
- Maximum current consumption (with 20mA signal) : 51mA at 24V
- Power dissipation within unit (with 20mA signal) : MTLx541 0.7W @ 24V dc, MTLx541S 1.0W @ 24V dc
- Safety description
Terminals 2 to 1 and 3: Uo=28V Io=93mA Po=651mW Um = 253V rms or dc
Terminals 1 to 3: Simple apparatus =1.5V, =0.1A and =25mW; can be connected without further certification into any IS loop with an open-circuit voltage <28V - Shipping Weight : 2 Kg