Sale!

CC-TUIO31 Honeywell Universal IO-2 non-redundant coated

CC-TUIO31 Honeywell Universal IO-2 non-redundant coated

Manufacturers :Honeywell
Model(s)  :CC-TUIO31
Additional Information :Universal IO-2 non-redundant coated
Estimated Shipping Size
Dimensions: 263 × 58 × 28mm
Weight:.4.3 kg
Country of Origin: United States of America

 

Categories: , SKU: CC-TUIO31

Description

Overview


Essential details:CC-TUIO31 Honeywell Universal IO-2 non-redundant coated

• High Level Analog Input /HART Input Module (16pt) – The High Level Analog Input Module supports both high level analog and HART inputs. Analog inputs are typically 4-20mA DC for both traditional and HART devices. HART data can be used for status and configuration. HART data, such as the secondary and tertiary variables, can also be used as process control variables. Two versions are available.
• High Level Analog Input w/o HART (16pt) – The High Level Analog Input Module supports high level analog inputs Analog inputs are typically 4-20mA DC for traditional devices.
• Analog Output/HART Output Module (16pt) – The Analog Output Module supports both standard 4-20mA DC outputs and HART transmitter outputs. Two versions are available.
• Analog Output w/o HART (16pt) – The Analog Output Module supports standard 4-20mA DC outputs.
• Digital Input 24 VDC (32pt) – Digital input sensing for 24V signals. Two versions are available.
• Digital Input High Voltage (32pt) – Digital input sensing for 110 VAC, 220 VAC, 125VDC.
• Digital Output 24 VDC (32 pt) – Current sourcing digital outputs. Outputs are electronically short-circuit protected. Two versions are available.
• Relay Digital Output (32 pt) – Digital output with NO or NC dry contacts. Can be used for low power or high power applications.
• Temperature Multiplexer (64 pt) – Provides thermocouple (TC) and resistance temperature device (RTD) inputs.
The Multiplexer supports up to four, field proven PMIO FTAs.
• Temperature Multiplexer (64 pt) – Provides thermocouple (TC) and resistance temperature device (RTD) inputs.
The Multiplexer supports up to four, field proven PMIO FTAs
• Pulse Input (8pt) – Provide linear counting, PV generation, and Quaduature Input for Custody Transfer
• Universal Input Output (32 pt) – Supports 32 channels of user configurable IO. Choices available – analog input, analog output, digital input, and digital output.

CC-TUIO31

lf you need to inquire or purchase ,please send the product models to my email or call medirectly .

sunny  He

[Email] sales@xiongbagk.cn

[Mobile] 86-18059884797

[WhatsApp] 86-18059884797

[Skype] sales@saulcontrol.com

CC-TUIO31 Honeywell Universal IO-2 non-redundant coated

Temperature Support
The Temperature Input LLMUX supports the existing solid state PMIO LLMUX FTA. The PMIO LLMUX FTA supports RTD and Thermocouple (TC) inputs. The Temperature variable is collected from all points at a 1 second rate. The 1 second update includes a configurable check for Open Thermocouple Detection (OTD) (see below) before propagation of the temperature variable. All TC inputs are compensated using a Cold Junction Compensation (CJT) device. Sampling and Open Sensor Detect
The Temperature multiplexer supports RTD and Thermocouples with Open Sensor Detect before PV delivered if so configured. With the OTD configuration active, the PV is sampled and held while an OTD cycle is performed within the same measurement window. If the OTD is negative, the PV is propagated up through the system. If the OTD is positive, the PV is set to NAN and the input channel soft failure is set. In this way, no inappropriate control action occurs for PV values that are invalid due to an open thermocouple. PV sampling/reporting incurs no added delays from OTD processing.