ABB PCD235B101 3BHE032025R0101 Generator Protection Relay

Parameter
Specification
Model / Order Code
PCD235B101 / 3BHE032025R0101
Manufacturer
ABB
Product Family
Relion® 670 Series (Specifically, a REG670​ variant)
Device Type
Numerical Generator Protection Relay (IED – Intelligent Electronic Device)
Key Protection Functions
This specific B101configuration typically includes a comprehensive suite, such as:
Stator Differential Protection (87G)
Backup Impedance Protection (21)
Stator Earth Fault Protection (100% & 95%, 59N/27TN)
Negative Sequence / Unbalance Protection (46)
Overcurrent (51, 51V)
Over/Under Voltage (59/27)
Over/Under Frequency (81O/U)
Loss of Excitation (40)
Reverse Power (32)
Voltage Restrained Overcurrent (51V)
Field (Rotor) Earth Fault Protection (64F)
Categories: ,

Description

ABB PCD235B101 3BHE032025R0101 Generator Protection Relay

Product Overview

The ABB PCD235B101, with the order code 3BHE032025R0101, is a numerical generator protection relay​ belonging to ABB’s renowned Relion® 670 series. This specific model, PCD235B101, is part of the REG670​ generator protection terminal family, which is designed to provide comprehensive, high-speed, and reliable protection for medium to large-sized synchronous generators​ in power plants and industrial facilities.
This device integrates multiple protection, control, measurement, and monitoring functions into a single, compact platform. It is engineered to safeguard the generator and the generator-transformer block against a wide range of electrical faults and abnormal operating conditions. The order code 3BHE032025R0101​ uniquely defines this hardware and firmware configuration, which includes a specific set of pre-configured protection functions and communication options. It represents ABB’s cutting-edge technology for ensuring the stability and availability of critical power generation assets.

Technical Specifications

Parameter
Specification
Model / Order Code
PCD235B101 / 3BHE032025R0101
Manufacturer
ABB
Product Family
Relion® 670 Series (Specifically, a REG670​ variant)
Device Type
Numerical Generator Protection Relay (IED – Intelligent Electronic Device)
Key Protection Functions
This specific B101configuration typically includes a comprehensive suite, such as:
Stator Differential Protection (87G)
Backup Impedance Protection (21)
Stator Earth Fault Protection (100% & 95%, 59N/27TN)
Negative Sequence / Unbalance Protection (46)
Overcurrent (51, 51V)
Over/Under Voltage (59/27)
Over/Under Frequency (81O/U)
Loss of Excitation (40)
Reverse Power (32)
Voltage Restrained Overcurrent (51V)
Field (Rotor) Earth Fault Protection (64F)
Measurement & Monitoring
• Three-phase currents & voltages, frequency, power (P, Q, S), power factor, energy.
• Sequence components.
• Extensive disturbance recording (DR) and event logging (SOE).
Inputs/Outputs
Analog Inputs:​ For CTs (e.g., 1A/5A) and VTs.
Binary Inputs:​ For breaker status, trip signals from other relays, etc.
Relay Outputs:​ Multiple contacts for trip, alarm, and control.
Communication Protocols
IEC 61850​ (Edition 1 & 2, including GOOSE​ and Sampled Values​ for process bus).
IEC 60870-5-103
Modbus RTU
DNP3.0
Profibus DP​ (optional via module)
Human-Machine Interface
Large graphical LCD display with keypad for local operation, browsing measurements, event logs, and settings.
Power Supply
Typically wide-range DC or AC (e.g., 48-250V DC / 110-240V AC).
Case Type
19-inch rack-mounted or flush-mounted case (size depends on I/O configuration).

PCD235B1101 3BHE032025R1101

Main Features and Advantages

  • Comprehensive, All-in-One Protection:​ Integrates virtually all standard and advanced protection functions required for a generator into one device, reducing panel space, wiring complexity, and engineering time compared to using multiple single-function relays.
  • High-Speed & High-Accuracy:​ Utilizes powerful processing and advanced algorithms (e.g., saturation detection for differential protection) to provide fast, secure, and dependable fault clearance, minimizing damage to the expensive generator asset.
  • IEC 61850 Native Support:​ As a core Relion® 670 series device, it natively supports IEC 61850​ for seamless integration into modern digital substations. This includes GOOSE​ for fast inter-relay communication and Sampled Values​ for connection to merging units, enabling a streamlined, fiber-optic based process bus architecture.
  • Advanced Monitoring & Diagnostics:​ Provides extensive metering, event recording with time synchronization (via IRIG-B or SNTP), and high-resolution fault recording. This data is crucial for post-event analysis, condition monitoring, and predictive maintenance.
  • Flexible Configuration:​ Engineered with ABB’s CAP 501/505​ configuration tools within PCM600​ software, allowing protection engineers to tailor logic, settings, and schemes to the specific generator’s characteristics and plant requirements.

Application Fields

The PCD235B101 / REG670​ is deployed as the primary protection for synchronous generators in:
  • Thermal Power Plants:​ Coal, gas, and combined-cycle power plants.
  • Hydroelectric Power Plants:​ For both large and small hydro generators.
  • Industrial Power Generation:​ Captive power plants in industries like petrochemicals, metals, and pulp & paper.
  • Nuclear Power Plants​ (in safety-class and non-safety-class applications with appropriate qualifications).
  • Renewable Integration:​ For protection of generators in bioenergy plants.

Related Products & System Integration

  • Current & Voltage Transformers:​ High-accuracy CTs and VTs for measurement and protection inputs.
  • Merging Units (MU):​ If used in an IEC 61850-9-2 process bus architecture.
  • Breaker & Switchgear:​ The circuit breaker which the relay trips to isolate the generator.
  • Excitation System (AVR):​ The REG670 communicates with or receives signals from the Automatic Voltage Regulator.
  • Governor:​ Coordinates with the relay for frequency/load control.
  • Plant DCS/SCADA:​ The relay communicates all its data (measurements, status, alarms) to the central control system via IEC 61850, Modbus, or DNP3.
  • Engineering & Maintenance Tool:ABB PCM600​ software with the appropriate REG670 Application Configuration​ for setting, monitoring, and disturbance analysis.
  • Time Synchronization Source:​ GPS clock for IRIG-B or SNTP time synchronization.