Description
ABB PCD235B101 3BHE032025R0101 Generator Protection Relay
Product Overview
The ABB PCD235B101, with the order code 3BHE032025R0101, is a numerical generator protection relay belonging to ABB’s renowned Relion® 670 series. This specific model, PCD235B101, is part of the REG670 generator protection terminal family, which is designed to provide comprehensive, high-speed, and reliable protection for medium to large-sized synchronous generators in power plants and industrial facilities.
This device integrates multiple protection, control, measurement, and monitoring functions into a single, compact platform. It is engineered to safeguard the generator and the generator-transformer block against a wide range of electrical faults and abnormal operating conditions. The order code 3BHE032025R0101 uniquely defines this hardware and firmware configuration, which includes a specific set of pre-configured protection functions and communication options. It represents ABB’s cutting-edge technology for ensuring the stability and availability of critical power generation assets.
Technical Specifications
|
Parameter
|
Specification
|
|---|---|
|
Model / Order Code
|
PCD235B101 / 3BHE032025R0101
|
|
Manufacturer
|
ABB
|
|
Product Family
|
Relion® 670 Series (Specifically, a REG670 variant)
|
|
Device Type
|
Numerical Generator Protection Relay (IED – Intelligent Electronic Device)
|
|
Key Protection Functions
|
This specific
B101configuration typically includes a comprehensive suite, such as:• Stator Differential Protection (87G) • Backup Impedance Protection (21) • Stator Earth Fault Protection (100% & 95%, 59N/27TN) • Negative Sequence / Unbalance Protection (46) • Overcurrent (51, 51V) • Over/Under Voltage (59/27) • Over/Under Frequency (81O/U) • Loss of Excitation (40) • Reverse Power (32) • Voltage Restrained Overcurrent (51V) • Field (Rotor) Earth Fault Protection (64F) |
|
Measurement & Monitoring
|
• Three-phase currents & voltages, frequency, power (P, Q, S), power factor, energy.
• Sequence components. • Extensive disturbance recording (DR) and event logging (SOE). |
|
Inputs/Outputs
|
• Analog Inputs: For CTs (e.g., 1A/5A) and VTs.
• Binary Inputs: For breaker status, trip signals from other relays, etc. • Relay Outputs: Multiple contacts for trip, alarm, and control. |
|
Communication Protocols
|
• IEC 61850 (Edition 1 & 2, including GOOSE and Sampled Values for process bus).
• IEC 60870-5-103 • Modbus RTU • DNP3.0 • Profibus DP (optional via module) |
|
Human-Machine Interface
|
Large graphical LCD display with keypad for local operation, browsing measurements, event logs, and settings.
|
|
Power Supply
|
Typically wide-range DC or AC (e.g., 48-250V DC / 110-240V AC).
|
|
Case Type
|
19-inch rack-mounted or flush-mounted case (size depends on I/O configuration).
|
Main Features and Advantages
-
Comprehensive, All-in-One Protection: Integrates virtually all standard and advanced protection functions required for a generator into one device, reducing panel space, wiring complexity, and engineering time compared to using multiple single-function relays.
-
High-Speed & High-Accuracy: Utilizes powerful processing and advanced algorithms (e.g., saturation detection for differential protection) to provide fast, secure, and dependable fault clearance, minimizing damage to the expensive generator asset.
-
IEC 61850 Native Support: As a core Relion® 670 series device, it natively supports IEC 61850 for seamless integration into modern digital substations. This includes GOOSE for fast inter-relay communication and Sampled Values for connection to merging units, enabling a streamlined, fiber-optic based process bus architecture.
-
Advanced Monitoring & Diagnostics: Provides extensive metering, event recording with time synchronization (via IRIG-B or SNTP), and high-resolution fault recording. This data is crucial for post-event analysis, condition monitoring, and predictive maintenance.
-
Flexible Configuration: Engineered with ABB’s CAP 501/505 configuration tools within PCM600 software, allowing protection engineers to tailor logic, settings, and schemes to the specific generator’s characteristics and plant requirements.
Application Fields
The PCD235B101 / REG670 is deployed as the primary protection for synchronous generators in:
-
Thermal Power Plants: Coal, gas, and combined-cycle power plants.
-
Hydroelectric Power Plants: For both large and small hydro generators.
-
Industrial Power Generation: Captive power plants in industries like petrochemicals, metals, and pulp & paper.
-
Nuclear Power Plants (in safety-class and non-safety-class applications with appropriate qualifications).
-
Renewable Integration: For protection of generators in bioenergy plants.
Related Products & System Integration
-
Current & Voltage Transformers: High-accuracy CTs and VTs for measurement and protection inputs.
-
Merging Units (MU): If used in an IEC 61850-9-2 process bus architecture.
-
Breaker & Switchgear: The circuit breaker which the relay trips to isolate the generator.
-
Excitation System (AVR): The REG670 communicates with or receives signals from the Automatic Voltage Regulator.
-
Governor: Coordinates with the relay for frequency/load control.
-
Plant DCS/SCADA: The relay communicates all its data (measurements, status, alarms) to the central control system via IEC 61850, Modbus, or DNP3.
-
Engineering & Maintenance Tool: ABB PCM600 software with the appropriate REG670 Application Configuration for setting, monitoring, and disturbance analysis.
-
Time Synchronization Source: GPS clock for IRIG-B or SNTP time synchronization.
1 Year Warranty
