Description
Product Description
The ABB P4RX (1KHW001356R0004) is a dedicated receiver‑filter module for the ABB ETL600 power‑line carrier communication system. It is installed in the right‑most slot of the P7LC channel sub‑rack, used to suppress interference signals generated by local transmitters and parallel‑channel transmitters. An integrated bypass circuit will automatically short‑circuit the signal path once the module is pulled out, so that carrier communication will not be interrupted during hot‑swap replacement. It guarantees stable transmission of tele‑protection signals, SCADA data and voice communication inside power substations.
Technical Specifications
| Item | Specification |
|---|---|
| Manufacturer | ABB |
| Model | P4RX (RX‑Filter) |
| Part Number | 1KHW001356R0004 |
| Device Type | Receiver Filter Module |
| Applicable System | ETL600 Power‑Line Carrier (PLC) Equipment |
| Mounting Slot | Right‑most slot of P7LC channel rack |
| Core Function | Suppress RF interference from local & parallel transmitters |
| Bypass Function | Auto short‑circuit, signal pass‑through after removal |
| Carrier Frequency Band | 10‑1000 kHz |
| Power Supply | Back‑plane bus power from P7LC rack |
| Weight | 0.25‑0.33 kg |
| Dimension (W×H×D) | 225 mm × 150 mm × 25 mm |
| Operating Temperature | -20℃ ~ +60℃ |
| Country of Origin | Sweden |
Key Features
- Built‑in hardware bypass circuit, hot‑swappable without breaking tele‑protection channels
- Optimized radio‑frequency filtering, improves signal‑to‑noise ratio for carrier receiver
- Compact plug‑in card‑type design for fast installation and on‑site maintenance
- Industrial‑grade hardware, suitable for long‑term continuous operation in substation environment
- Standard spare component of ABB ETL600 carrier communication solution
Product Introduction
The ABB P4RX 1KHW001356R0004 is identified as a P4RX RX Filter, indicating a filtering function associated with an RX signal path rather than a programmable PLC or conventional process I/O module. The exact ABB ordering code is important because public records for this part are limited and do not provide enough reliable information to establish universal voltage, current, frequency, or connector specifications.
From a maintenance standpoint, this component should be treated as a system-specific ABB filter assembly. Its electrical behavior depends on the equipment in which it is installed. Replacing it solely on the basis of physical appearance or a generic “RX filter” description can introduce an incorrect impedance, attenuation characteristic, or interface configuration into the signal chain.
Application Scenarios & Field Pitfalls — Engineer’s Perspective
The P4RX 1KHW001356R0004 is most relevant to maintenance of ABB equipment where the P4RX filtering stage forms part of an existing signal or control architecture. A filter of this type may be used to suppress unwanted signal components or condition an RX path before the receiving electronics process the signal, but the exact circuit role should be established from the parent equipment drawings rather than inferred from the short product designation.